About Established in 2020 Om Prasanth Industries established 2020 is...
Read MoreSUBMERSIBLE PUMP TROUBLESHOOTING TIPS
IF MOTOR CAUSES ANY PROBLEM WERE ITS SOLUTION IS GIVEN BELOW
Find your problem and then click dropdown icon (↓) to see the solution
No power supply | Check power supply. |
Very low voltage | Check the input supply wire capacity (size) whether it is adequate for the given load and also check for any loose Connections. Consult Power supplier for low voltage supply. |
Fuse blown up | Check for voltage at motor terminal replace fuse. If new fuse also blows out, recheck all electrical wiring |
Capacitor failure | Replace capacitor |
Motor protector is open due to over heating | Check free rotation of the rotor by rotating the shaft. Check supply voltage. Check pump input current. |
Impeller stuck | Check and correct it. Cover the foot valve or stainer with a close meshed strainer to avoid foreigh particles entering into the pump. |
Broken circuit in incoming leads | Check all circuits and remedy fault. |
Possible Cause | Check | Corrective Action | |
---|---|---|---|
Pump may be air locked | Stop and start the pump several times, waiting about one minute between cycles. If the pump then resumes normal delivery, air lock was the trouble. | If this test fails to correct the trouble, proceed with the steps that follow. | |
Low voltage | Check voltage at control box with pump running. Check incoming wire size and power supply wire size against chart in your manual. | Install larger wire from meter to control box. Install larger wire from control box to pump. If necessary, have power company raise power supply voltage. | |
Water level in well too low | Amount of water in well (recovery rate) may be too low for pump capacity. Restrict the flow of pump output, then wait for well to recover and start pump. | If partial restriction corrects trouble, leave valve or cock at restricted setting. Otherwise, lower pump in well if depth is sufficient. Do not lower if sand clogging might occur. | |
Discharge line check valve installed backward | Examine check valve on discharge line to make sure that the arrow indicating direction of flow points in the right direction. | Reverse the valve, if necessary. | |
Leak in drop pipe | Raise the pipe and examine for leaks. | Replace the damaged section of drop pipe. | |
Pump check valve jammed by drop pipe | When pump is pulled after completing step 5, examine connection of drop pipe to pump outlet. If threaded section of drop pipe has been screwed in too far, it may be jamming the pump’s check valve in the closed position. | Unscrew the drop pipe and cut off a portion of threads. | |
Pump intake screen blocked | The intake screen on the pump may be blocked by sand or mud. Examine. | Clean the screen and when reinstalling the pump, make sure that it is located several feet above the well bottom-preferably 10 feet or more. | |
Pump parts worn | The presence of abrasives in the water may result in excessive wear on the impeller, casing and other close-clearance parts. Before pulling the pump, reduce setting on pressure to see if the pump shuts off. If it does, worn parts are probably at fault. | Pull the pump and replace worn components.. | |
Motor shaft uncoupled | Coupling between motor and pump shaft may have worn out or worked loose. Inspect for this after pulling the pump and looking for worn components, as in step 8. | Tighten all connections and setscrews. Replace parts if worn out. |
Kept idle for long time | Rotate the pump shaft with a screwdriver inserting it in the slotted portion of the shaft, which is provided at cooling fan side of the motor. If this is not enough to solve the problem, unscrew the bold and rinse/clean the pump thoroughly until the pump shaft rotates freely by hand. Pump should be run for few minutes atleast once in three days. |
Priming is not sufficient | Fill water completely and ensure priming plug is tightened well. |
Too many bends & elbows in suction & delivery pipe line | Reduce bends & elbows as much as possible. |
Suction Lift too high | Install the pump closer to the water level. Suction lift to be within recommended depth. |
Foot valve or inbuilt check value in regenerative monoset self priming pump is not fuctioning. | Repair or replace it. |
Wrong direction of rotation | Correct the direction of rotation to coincide with direction indicated by the arrow mark on the pump. |
Total head higher than the specified one | Reduce the total head or change to a suitable range pump. |
Air being sucked in through the suction pipe line | Check the pipe for leakage and correct it. |
Leakage in air cock | Tighten the air cock. If necessary replace it. |
Smaller size pipes used | Change the pipes to the recommended sizes |
Mechanical seal leaking | Change the mechanical seal |
Foot valve or impeller or pipe blocked | Clean the pipe, impeller and foot valve |
Low voltage | Check the supply wire capacity (size) and also check for any loose connections. Contact the power supplier to rectify low voltage. |
Possible Cause | Check | Corrective Action | |
---|---|---|---|
Water level in well too low | The wells ability to deliver water to the pump may be too low for the pump capacity. Restrict the flow of pump output, wait for the well to recover, and then start pump. | If partial restriction corrects trouble, leave the valve or cock at restricted setting. Otherwise, lower pump into well if depth is sufficient. Do not lower if sand clogging might occur. | |
Leak in drop line | Raise the pipe and examine for leaks. | Replace the damaged section of the drop pipe. | |
Pump parts worn | The presence of abrasives in the water may result in excessive wear on the impeller, casing and other close-clearance parts. Before pulling the pump, reduce setting on pressure to see if the pump shuts off. If it does, worn parts are probably at fault. | Pull the pump and replace worn components. |
Problem | Check | Correct |
---|---|---|
Defective pressure switch on submersible pump or pressure switch not adjusted properly | Examine pressure setting switch for defects. Readjust pressure switch when necessary. | Replace pressure switch on submersible pump or reduce pressure setting. |
Pressure tank leaks above water level | Apply a soapy mixture to the whole tank surface of the submersible pump. Bubbles indicate that air is escaping. | Replace submersible pump tank. |
Plumbing system leak in submersible pump | Service line should be examined for leaks. | Repair leaks in service line. |
Leak in discharge line check valve | Remove and inspect. | Replace discharge line if necessary. |
Plugged air volume control on submersible pump | Remove and examine air volume control | Replace air volume control on submersible pump |
Plugged snifter valve on submersible pump | Remove and inspect snifter valve. | Replace snifter valve on submersible pump. |
Possible Cause | Check | Corrective Action | |
---|---|---|---|
Incorrect voltage | Check overloads and circuit breaker to see of they are operable. | Reset overloads or circuit breaker. | |
No Power | Check power supply to control box (or overload protection box) by placing a voltmeter across the incoming power lines. Voltage should approximate nominal line voltage. | If no power is reaching box, contact power company for service. | |
Defective control box | Examine wiring in the control box to make sure all contacts are tight. With a voltmeter, check voltage at line and motor terminals. If no voltage is shown at terminals, wiring is defective from pressure switch or in control box. | Correct faulty wiring or tighten loose contacts. | |
If Pump still not running contact Customer Service | Check the resistance of the motor winding by using an ohmmeter on the proper terminals in the control box (see manufacturer’s wiring diagram). The resistance should match the ohms specified in the manufacturer’s data sheet. If too low, drop wire sized wrong or bad windings . | If neither cable or winding is defective-shorted, grounded or open-the pump must be pulled and serviced. |
Mechanical seal improperly fitted or damaged. Check valve / foot valve malfunctioning. | Check seal, correct and replace if required |
Bearing worn out / incorrectly fitted | Replace bearing and use recommended quality grease |
Vibration of pipes with support | Securely hold pipe lines |
Impeller blocked | Clean impeller |
Shaft bend | Rectify or replace it |
Check valve / foot valve malfunctioning | Rectity or replace |
Problem | Check | Correct |
---|---|---|
Pressure switch on the submersible pump is defective | Pressure switch points may have adhered to each other causing the switch to remain in a closed position. | Clean the points on the pressure switch. If this does not work, the switch on the submersible pump needs to be replaced. |
Drop line has a leak | Raise the pipe on the submersible pump and check for leaks. | The damaged section of the drop pipe should be replaced. |
Level of water in well is too low | Restrain the output flow of the submersible pump, then wait for the well to recover. Re-start the pump. | Keep the valve at the restricted setting if this has remedied the problem. If not, the submersible pump must be lowered further down in the well. |
Submersible pump parts are damaged | The impeller, casing, and other parts of the submersible pump may be worn due to abrasives in the water. Lower the pressure switch setting. If the pump shuts off, damaged parts are the probable cause.. | Replace worn parts on the submersible pump. |
Problem | Check | Correct |
---|---|---|
Submersible pump may be air-locked | Start and stop pump repeatedly. If submersible pump begins working, air lock was the problem. | If the trouble isn’t corrected by performing this test, move on to the next possible problem. |
Water level too low in submersible pump | Well production could be too low. Limit flow of pump output, then wait for well to recover and re-start. | If partial limitation of flow corrects the problem leave the valve at the restricted setting. |
Discharge line check valve installed backwards on submersible pump | Make sure arrow that indicates direction of flow on check valve is pointed in the right direction. | If check valve is not pointed in the right direction, then reverse the valve. |
Drop pipe leaks | Lift up pipe and inspect for leaks | Replace the damaged part of drop pipe |
Blocked pump intake screen | Examine intake screen on the submersible pump and check for mud or sand blockage. | Clean screen and make sure submersible pump is reinstalled many feet above the well bottom. |
Drop pipe jamming submersible pump check valve | Raise pump to inspect drop pipe connection to pump outlet. Threaded area of drop pipe may be screwed in too far, jamming the check valve in a closed position. | Loosen the drop pipe and cut off a portion of the threads. Then screw it back on the pipe, freeing the submersible pump check valve. |
Worn pump parts | Reduce setting on pressure switch to see if the submersible pump shuts off. If it does, check for worn parts | Pull submersible pump and replace the worn components. |
Loose motor shaft | Pull up submersible pump to inspect the motor shaft. | Re-tighten all of the connections. |
Problem | Check | Correct |
---|---|---|
Power is not supplied to the submersible pump | Place a voltmeter across power lines coming into the submersible pump to check the power supply for the overload protection box. | The power company should be consulted if there is no power to the box. |
There is no overload protection | Examine the circuit breaker and the fuses to the submersible pump to ensure that they are operating correctly. | Replace blown fuses and reset the breaker if it has been tripped. |
Pressure switch on submersible pump is damaged | With the submersible pump pressure switch in a closed position, check the voltage across the switch. If the voltage drop is at the same level as the line voltage, the switch is obviously not making contact. | The contact points should be cleaned and/or the pressure switch replaced for the submersible pump. |